Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/26/2000 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 09/25/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* |
| 09/21/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/NEED ALL PREVIOUS INSPECTION REPORTS REMOVE ALL INSULATION RECALL WHEN READY. |
| 09/18/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0925*/1. ENRTY PORCH COLUMN NOT INSTALLED. 2. STUD MISSING AT GARAGE EXTERIOR WALL SPAN EXCEEDS 16" O.C. 3. WIRING WILL HAVE TO BE REMOVED FOR STUD. 4. RED HEAD ANCHOR BOLTS LOOSE. 5. FIREBLOCK REQUIRED BY DRYER VENT. 6. ANCHOR BOLTS MISSING AT KITCHEN WALL. THROUGHOUT HOUSE. 7. F/BLOCK WALLS AT 10 FT. NO PLANS OR PERMIT ON SITE STOPPED INSPECTION. |