Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/15/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/08/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ CPUC HOT WATER 1) NEED DOUBLE IN CONCEALLED SPACE, FLUE WATER HEATER 2) CPU FOR HOT WATER 3/4" 3) 50 SQUARE IN OF RELIEF DUCT WATER HEATER |
| 11/05/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
1.) CLAMP TO PIPE IS OK HAS A U.L. STAMP 2.) CLAMP AT COPPER GRO BOND ISNT AN APPROVED CLAMP ASK FOR CORRECT CLAMP AT THE STORE YOU BUY FROM |
| 09/27/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) WRONG SIZE FEEDERS FOR 200 AMP PANEL NNED 2/0 W OR 4/0 AL. (INVESTIGATE MAIN LUGS, MISSING UL LABEL 2) GAS LINE NOT SIZED OR TESTED, PIPE ON ROOF (INSIDE LINES WHERE TESTED) 3) WILL NEED TO CALL FOR FINAL WHEN THESE ITEMS RESOLVED |