Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T00CM03508
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/13/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
04/16/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* | |
04/03/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*KITCHEN EXHAUST HOOD MUST BE TYPE I HOOD AS PER SEC. 508. 2.) STORE DOES NOT MEET MANUFACTURERS INSTALLATION INSTRUCTIONS ON CLEARANCE FROM COMBUSTIBLE. | |
04/02/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1.) PROVIDE SECONDARY DRAIN ON AIR HANDLER ABOVE CEILING. HOOK UP CONDENSATE TO SMALL REMOT FAN COIL. 2.) PROVIDE GREASE PAN ON EXHAUST FAN ON ROOF. NEED TO SEE INSIDE OF SHAFT. 3.) FINISH HOOKING UP ELECTRICAL TO APPLIANCES. 4.) RAISE SEWER VENT 2' ABOVE EVAP COOLERS. 5.) PROVIDE MIN. 3" CLEARANCE AROUND GREASE DUCT. TYPE I HOOD REQUIRES 3" SPACING FROM WALL. |