Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/12/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 09/10/2001 |
FRAMING |
|
Partial Approval |
|
| 09/07/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) LAV TRAP ARM EXCEEDS 60" TO VENT OPENING AND WEIR OF TRAP HIGHER THAN VENT OPENING (RE-VENT) 2) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF WALL SURFACE 3) SMOKE DETECTOR CANNOT BE LOCATED WITHIN 36" OF AIR REGISTER 4) BACK GROUT/SEAL FLOOR PENETRATION FOR TUB 5) NO INSULATION UNDER TAPE AT DUCT "Y" 6) ANCHOR BOLTS MISSING NUTS 7) SUPPORT 1 1/2 DWV VENT AT ROOF PENETRATION. REVERSE PITCH 8) NO PLAN ON SITE |