Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
09/12/2001 FRAMING Approved IVRS - Inspection 0000*
09/10/2001 FRAMING Partial Approval
09/07/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) LAV TRAP ARM EXCEEDS 60" TO VENT OPENING AND WEIR OF TRAP HIGHER THAN VENT OPENING (RE-VENT) 2) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF WALL SURFACE 3) SMOKE DETECTOR CANNOT BE LOCATED WITHIN 36" OF AIR REGISTER 4) BACK GROUT/SEAL FLOOR PENETRATION FOR TUB 5) NO INSULATION UNDER TAPE AT DUCT "Y" 6) ANCHOR BOLTS MISSING NUTS 7) SUPPORT 1 1/2 DWV VENT AT ROOF PENETRATION. REVERSE PITCH 8) NO PLAN ON SITE