Inspection History: ELECTRIC - FINAL
Permit Number - T00CM03486
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/15/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
09/13/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* PLAN CALLS OUT FOR C FIXTURES TO HAVE BATTERY BACK UP SOUTH SUB PANEL COVERS FOR INSPECTION UPDATE PANEL SCHEDULES |
|
09/08/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* OK TO CLEAR TEMP POWER CONTINGENT ON POSTING C OF O BOND |
|
09/07/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* ABOVE CEILING APPROVED SERVICE CONDUITS, CABINATES REQUIRE BOND BUSHINGS PER 250-94 N.E.C. BOND NEUTRAL IN DISCONNECT SWITCH |
|
09/05/2000 | ELECTRIC - FINAL | Partial Approval | FRONT AREA OK BACK ROOMS NEED ADDTIONAL CONDUIT SUPPORT WITHIN 3' EVERY J-BOX |