Permit: T00CM03486

Parcel: 12110005D


Addresses:

4752 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/15/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
09/13/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
PLAN CALLS OUT FOR C FIXTURES TO
HAVE BATTERY BACK UP
SOUTH SUB PANEL COVERS FOR INSPECTION
UPDATE PANEL SCHEDULES
09/08/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
OK TO CLEAR TEMP POWER CONTINGENT ON POSTING C OF O BOND
09/07/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
ABOVE CEILING APPROVED
SERVICE CONDUITS, CABINATES REQUIRE BOND BUSHINGS PER 250-94 N.E.C.
BOND NEUTRAL IN DISCONNECT SWITCH
09/05/2000 ELECTRIC - FINAL Partial Approval FRONT AREA OK
BACK ROOMS NEED ADDTIONAL CONDUIT SUPPORT WITHIN 3' EVERY J-BOX