Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2000 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000* 1. NEED TO SEE REVISED DRAWING SHOWING " AS BUILT" AT CONNECITON TO EXISTING 2. UNDERGROUND ABS OK 3. TIE IN AT EXISTING OK 4. WATER TEST TO 42" OK 5. OK TO COVER |
|
| 09/22/2000 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* 1. FURNCO COUPLINGS NOT APPROVED UNDER SLAB MUST BE SHIELDED COUPLINGS ( MISSION) 2. 2 WAY C.O. IS SURFACE C.O. ONLY INSTALL DIRECTIONAL C.O. WITH WYE BRANCH FITTING PLAN CHANGED AT LAVATORY WATER CLOSET VENT MUST BE DOWNSTREAM OF TRAP |