Permit: T00CM03470

Parcel: 10602255A


Addresses:

3650 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00CM03470

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/04/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/05/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* WORKING CLEARANCES IN FRONT OF MAIN SERVICE PANEL A AND B
12/29/2000 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
CALLED IN CANCELED
12/28/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
NEED PAPER WORK LISTING PANEL "A" TO USE WITH BACK FIELD 100 AMP MAIN BREAKER NEED BREAKER
FINISH PREVIOUS INSPECTION REPORT
UNDERGROUND TO SIGN BURIED
12/28/2000 ELECTRIC - FINAL Partial Approval OK FOR TEMP C/O
SUBJECT TO TRANSFER OF BOND
BACKFED DEVICE TO BE SECURED IN PLACE 284-16 (G)
12/27/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
12/22/2000 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
12/21/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
SERVICE CONDUCTORS NOT AS LISTED ON PLANS
NEED SERVICE LABELING AS PER PLANS
PLANS CALL FOR BOLT ON BREAKERS
NEED PERMANENT CIRCUIT DIRECTORIES
FRONT PORCH NOT READY
CAN TRIMS NOT LISTED FOR ROW BULBS
FINISH INSTALL SOUTH ROOF MOUNTED LIGHT
12/21/2000 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
12/19/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
SERVICE CONDUCTORS NOT AS LISTED ON PLANS
NEED R CLIPS ON SQUARE ON SQUARE "D" DISCONNECTS
NEED LABLING AS PLASN
LABEL DISCONNECTS AS TO WHICH PANEL
EMT STRAP COMING OUT OF WALL
BREAKERS TO BE BOLT ON AS PER PLAN
NEED PERMANENT CIRCUIT DIRECTORY
STRAP FLEX AND TIGHTEN FITTINGS AT WATER HEATER NEED DISCONECTING MEANS
FRONT PORCH NOT READY
CAN TRIM NOT LISTED FOR 120 W BULB
ROOF
HAVE MECHANICAL INSPECTOR VERIFY FUSES
SEAL ALL UNSED OPENING
WORKING CLEANCES IN FRONT UNIT #3
LIGHTING ON BACK OF BUILDING TO MEET OUTDOOR LIGHTING CODES