Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date |
Description |
Inspector |
Results |
Comments |
| 11/21/2000 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Approved |
IVRS - Inspection 0000* |
| 10/27/2000 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999*/1. ALL OUTSIDE ELECTRIC OUTLETS MUST BE GFCI PROTECTED. 2. ALL EXPOSED N.M.C. ELECTRIC CABLE BELOW 8' MUST BE PHYSICALLY PROTECTED. 3. OPEN ALL ELECTRIC JUNCTION BOXES FOR INSPECTION OF GROUNDING OF METAL BOXES. 4. N.M.C. MUST BE PROTECTED AT METAL BOX KNOCK OUTS. INSTALL ROMEX CLAMPS AND GROUND BOXES. 5. POST FOOTER MUST BE 12" X 12" IN BY 12" DEEP. 6. 14-2 ON 20 AMP BREAKER. |