Permit: T00CM03432

Parcel: 13314459C


Addresses:

6400 E EL DORADO CI


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T00CM03432

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/04/2000 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*
WASTE AND VENT SYSTEM OK
OVERHEAD WATER DISTRIBUTION OK
ALL CORRECTIONS HAVE BEEN MADE
OK FOR DRYWALL UPON BLDG INSPECTORS APPROVAL
10/03/2000 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*
HORIZONTAL RE VENTS ARE OVERLOADED COUNT FIXTURE UNITS THEN INCREASE ACCORDINLY
MUST HAVE SPECIALTY COUPLING WHERE 3" ABS CONNECTS TO 2" C.I.
09/25/2000 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*
1. 2" VENT IS OVERLOADED. MAX FIXTURE UNITS ON 2" VTR IS 24 F.O.
2. MIN SIZE OF VENT FOR WATER CLOSET IS 2" FOR WATER CLOSET IN RM 105. CAN NOT CONNECT TO EXSISTING 1 1/2" VENT