Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2000 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* WASTE AND VENT SYSTEM OK OVERHEAD WATER DISTRIBUTION OK ALL CORRECTIONS HAVE BEEN MADE OK FOR DRYWALL UPON BLDG INSPECTORS APPROVAL |
|
| 10/03/2000 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* HORIZONTAL RE VENTS ARE OVERLOADED COUNT FIXTURE UNITS THEN INCREASE ACCORDINLY MUST HAVE SPECIALTY COUPLING WHERE 3" ABS CONNECTS TO 2" C.I. |
|
| 09/25/2000 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1. 2" VENT IS OVERLOADED. MAX FIXTURE UNITS ON 2" VTR IS 24 F.O. 2. MIN SIZE OF VENT FOR WATER CLOSET IS 2" FOR WATER CLOSET IN RM 105. CAN NOT CONNECT TO EXSISTING 1 1/2" VENT |