Permit: T00CM03412

Parcel: 12601003C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/13/2000 ELECTRIC - FINAL Approved VERIFIED SPLICES IN SUMP RATED FOR SUBMERSIBLE APPLICATIONS 3,M SPLICE
10/12/2000 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
CONDUIT AND WIRING NOT COMPLETE FOR LOADING DOCK PUMP
EMT CONDUIT TO BE SUPPORTED WITHIN 3' OF BOXES, AND 10' ENTER VALS
BX OR MC CABLE SUPPORTED WITHIN 1' EVERY BOX AND 6' INTERVALS
UPDATE PANEL SCHEDULES
BOX OFFSETS ON SURFACE MTD. CONDUITS TO BOXES.
LOOSE FITTINGS
INSTALL WATER TITE J-BOX IN 50 MP CONTAINMENT AREA AND SPLICES MUST BE APPROVED FOR SUBMERSION IN WATER