Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/05/2001 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* THIS APPROVAL IS FOR TRUNK LINE ONLY. THIS PLUMBING SYSTEM WILL NEED TO BE TESTED (WATER) AGAIN AT TIME OF INTERMEDIATE |
| 03/02/2001 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 02/23/2001 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999* 1) NOT INSTALLED AS PER PLAN 2) SANTEC NOT TO CODE PLEASE SEE SEC 706.4 VERTICAL TO HORIZONTAL 3) FLAT VENTING OF W/C NOT TO CODE 4) PLEASE PROVIDE 1/4" PER FT ON WASTE LINE 5) TEST DOWN AT THIS TIME PLEASE PROVIDE A MINIMUM OF 42". 6) DO NOT COVER |