Permit: T00CM03387

Parcel: 123081280


Addresses:

2705 E HELEN ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
09/12/2001 FRAMING Approved IVRS - Inspection 0000*
09/07/2001 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) CLOSET LIGHT SWITCHES BOXES NOT IN 2) CLOSET LIGHT SWITCHES BOXES NOT IN 3) CONVENIANCE OUTLET REQUIRED 6' FROM DOOR AND 12' THERE AFTER 4) HORIZONTAL VENT NOT ALLOWED BELOW 6" ABOVE FLOOD RIM AT KITCHEN 5) OK TO INSULATE AND DRYWALL ALL BUT REPAIR AREAS
09/05/2001 FRAMING Denied IVRS - Inspection 0950*/ 1) REVISE PLAN FOR ADDED GLUE LAM BEAM (5 3/4 X 15) BEARING ON ADOBE WALL ON EAST WALL AND BRICK WALL ON WEST SIDE SUPPORTED BY 2" LINTAL 2) REVISE PLAN FOR ADDED PORCH AT ENTRY 3) PLAN CALLS FOR 7050-5050 INSTALLED, ADDED 1650 AND 4040 AND POOR LOCATION NOT PER PLAN IN GUEST ROOM 4) W/C FLOOR FLANGE NOT INSTALLED 5) EXHAUST FAN MUST EXHAUST OUTSIDE 6) GUEST ROOM WATER CLOSET NOT PROPERLY VENTED 7) SHOWER REQUIRES A TEMPERATURE PRESSURE BALANCED ANTI-SCALD VALVE 8) REVISE PLAN FOR ADDED WATER HEATER IN GUEST ROOM CLOSET 9) REVISE PLAT TO AS BUILT