Permit: T00CM03379

Parcel: 11708211F


Addresses:

1055 S 10TH AV


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T00CM03379

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/09/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*
08/06/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) 712.2 4UPC TESTING 2.) 905.5 VENT OPENING 3.) 601 BACK FLOW AND CROSS CONNECTION 4.) 606.2.2 PVC FEMALE FITTINGS 5.) 906.1 VENT FLASHING 6.) MODULAR BUILDING SET ON SITE DOES NOT MEET MINIMUN INSTALLATION STANDARDS SEE 5 NOTES ABOVE. WHETHER OR NOT THE STATE APPROVED THIS MODULAR, IT DOES NOT MEET LOCAL CODES MAKE CORRECTIONS AND RE-CALL INSPECTION.
07/31/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*
07/31/2001 PLUMBING - FINAL Denied 1.) NO WATER TEST ON PVC DWV. 2.) FURNCO NOT APPROVED CONNECTOR FOR PVC X PVC 3.) THE POINT OF VENT CANNOT BE BELOW THE WEIR OF THE TRAP 4.) ALL HOSE BIBBS REQUIRE VACUUM BREAKERS 5.) FEMALE SCREWED PVS FITTINGS NOT ALLOWED ON WATER PIPING 6.) NO FLASHING ON PVC VENT.