Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T00CM03379
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/09/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
08/06/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) 712.2 4UPC TESTING 2.) 905.5 VENT OPENING 3.) 601 BACK FLOW AND CROSS CONNECTION 4.) 606.2.2 PVC FEMALE FITTINGS 5.) 906.1 VENT FLASHING 6.) MODULAR BUILDING SET ON SITE DOES NOT MEET MINIMUN INSTALLATION STANDARDS SEE 5 NOTES ABOVE. WHETHER OR NOT THE STATE APPROVED THIS MODULAR, IT DOES NOT MEET LOCAL CODES MAKE CORRECTIONS AND RE-CALL INSPECTION. | |
07/31/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* | |
07/31/2001 | PLUMBING - FINAL | Denied | 1.) NO WATER TEST ON PVC DWV. 2.) FURNCO NOT APPROVED CONNECTOR FOR PVC X PVC 3.) THE POINT OF VENT CANNOT BE BELOW THE WEIR OF THE TRAP 4.) ALL HOSE BIBBS REQUIRE VACUUM BREAKERS 5.) FEMALE SCREWED PVS FITTINGS NOT ALLOWED ON WATER PIPING 6.) NO FLASHING ON PVC VENT. |