Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T00CM03379

Parcel: 11708211F


Addresses:

1055 S 10TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T00CM03379

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
08/13/2001 ELECTRIC - UNDERGROUND Approved IVRS - Inspection 0000*ELEC UNDERGROUND OK YOU WILL NEED TO POUR A CONCRETE AND 6" THICK OVER PVC CONDUIT THAT IS NOT 18" DEEP. I NEED COMPACTION REPORTS & YOU NEED TO EXPOSE A COUPLE OF LOCATIONS SO I CAN SEE FILL.
08/09/2001 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection 0000*NOT READY PIPE NOT IN