Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T00CM03379
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/13/2001 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection 0000*ELEC UNDERGROUND OK YOU WILL NEED TO POUR A CONCRETE AND 6" THICK OVER PVC CONDUIT THAT IS NOT 18" DEEP. I NEED COMPACTION REPORTS & YOU NEED TO EXPOSE A COUPLE OF LOCATIONS SO I CAN SEE FILL. | |
08/09/2001 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection 0000*NOT READY PIPE NOT IN |