Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/29/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000$ |
| 09/26/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/1. NEW 2 X 10 RAFTERS CANNOT BEAR ON EXISTING 2 X 6 RAFTERS AT WEST SIDE OF ADDITION. PROVIDE APPROVED REPAIR DETAIL. 2. 2X BLOCKING MISSING AT BRACED WALL PANELS PER NOTE 44. 3. PAHD 42 HOLD DOWNS MUST BE NAILED TO FULL LENGTH DOUBLE STUDS SEE SIMPSON INSTALLATION MANUAL. 4. ANCHOR BOLTS ARE REQUIRED AT 6 FT ON CENTER MINIMUM ROOF IS UNSAFE TO CLIMB ON UNTIL PROPER BEARING IS ON WEST END AND BLOCKED ON EAST END. |