Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM03324
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/15/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* NOTE TO OWNER: NUMEROUS VIOLATIONS ABOVE CEILING - DATA CABLE ON CEILING, OPEN BOXES, EXPOSED CONDUCTORS, TRASH ON TILES, ETC... A ONE HOUR REPAIR PERMIT WILL NEED TO BE OBTAINED. THIS NEEDS TO BE TAKEN CARE OF AT THIS TIME. | |
12/21/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* LOOSE M/C FITTINGS INSTALL M/C CABLE INTO FITTINGS ATTACH ALL FIXTURES TO GRID 1X1 AND 1X2 USE MANUFACTURES, APPROVED DUST CAPS AS PER PLAN NEED GROUNDING EQUIPMENT CONDUTOR |
|
12/20/2000 | ELECTRIC - FINAL | Denied | WILL HAVE TO CHECK PROPER LISTING AND APPROVAL FOR THIS WIRING SYSTEM. THIRD PARTY CERTIFICATION | |
11/15/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* ATTACH FIXTURES TO GRID CAP EXPOSED CONNECTIONS AT END CONNECTORS REMOVE OLD WIRING SYSTEM NEED SUPPORT WIRES ON ALL FIXTURES NEED GROUNDING EQUIPMENT CONDUTOR |