Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 03/16/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* ALL INDICATIONS AT SERVICE INDICATE A HIGH LEG DELTA SYSTEM. SINGLE PHASE 2 WIRE CIRCUITS ARE INSTALLED IN THE IDENTIFIED HIGH LEG CIRCUIT. PLANS INDICATE A SINGLE PHASE EXSIST PANEL BOARD WHICH IS INCORRECT. PANEL SCHEDULE, PANEL BOARD AND CIRCUITS WILL HAVE TO BE RECONFIFURED TO INDICATE EXSIST. WIRES TO BE MOVED ACCORDINGLY TO PREVENT HIGH VOLTAGE AT 120 VOLT CIRCUITS CORRECT ADDRESSING AT SERVICE TO COINSIDE WITH PLANS | |
| 02/08/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* WHAT ARE THE TWO MC CABLES IN THE BACK ROOM FOR STILL UNFINISHED |