Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
Permit Number - T00CM03265
Inspection Description - ELECTRIC - SERVICE RELOCATION
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2001 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection 0000* | |
| 08/28/2001 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection 0000*1.) NEED FAULT CURRENTS ON PLANS 2.) NEED A/C OF EQUIPMENT ON PLANS 3.) BOND CONDUIT FOR LINE SIDE AS PER CODE 250-102 (0) 4.) ELEVATOR TRANSFORMER CANNOT STACK LUGS USE FULL SURFACE CONTACT OK ELEVATOR SHUNT TRIPS,PANEL, & CONTROLLER. * LEFT CUSTOMER WITH PAPER WORK REGARDING TEMP POWER. |