Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date |
Description |
Inspector |
Results |
Comments |
| 12/05/2001 |
ELECTRIC - SERVICE RELOCATION |
|
Approved |
IVRS - Inspection 0000* |
| 08/28/2001 |
ELECTRIC - SERVICE RELOCATION |
|
Partial Approval |
IVRS - Inspection 0000*1.) NEED FAULT CURRENTS ON PLANS 2.) NEED A/C OF EQUIPMENT ON PLANS 3.) BOND CONDUIT FOR LINE SIDE AS PER CODE 250-102 (0) 4.) ELEVATOR TRANSFORMER CANNOT STACK LUGS USE FULL SURFACE CONTACT OK ELEVATOR SHUNT TRIPS,PANEL, & CONTROLLER. * LEFT CUSTOMER WITH PAPER WORK REGARDING TEMP POWER. |