Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date |
Description |
Inspector |
Results |
Comments |
| 05/14/2002 |
ELECTRIC - UFER |
|
Approved |
|
| 03/05/2002 |
ELECTRIC - UFER |
|
Partial Approval |
IVRS - Inspection 0000*OK #3/0 TO 2 GROUND RODS OK 2-4" PVC FEEDERS OK 2- 3/4 PVC TO CARPORT LIGHTING. |
| 01/17/2002 |
ELECTRIC - UFER |
|
Denied |
IVRS - Inspection 0999*RE BAR IN FOOTING TO BE AT LEAST 20' IN LENGTH SINGLE PIECE IS ONLY 18' |