Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2000 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000* BLDG DRAIN HAS BEEN RAISED TO MANTAIN 45 DEGREE FROM BOTTOM OF FOOTER OK TO BACKFILL TRENCH |
|
| 12/04/2000 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* MUST HAVE APPROVED DRAWING ON BACKFILL OF TRENCH IN REFERANCE TO SECTION 131.3 94 UPC SOIL WATER TEST FOR ROUGH PLDG IN BLDG OK SOIL WATER TEST FOR RAN LEADERS OK OK TO BACKFILL BLDG SEWER HCS CONNECTION AND BLDG SEWER WATER TEST OK |
|
| 12/01/2000 | PLUMBING - ROUGH, SOIL | Cancelled | IVRS - Ri canceled | |
| 11/28/2000 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* MUST REMOVE 4" TEST TEE AT HCS CONNECTION THERE CAN BE NO THREADED FITTINGS UNDER GROUND CAN NOT USE TWO WAY C.O. FITTING WITH A EXTENSION ON IT. TWO WAY C.O. MUST BE DIRECTION AL FITTINGS BLDG. DRAIN IS TO CLOSE TO STRUCTURE FOOTING SEE SECTION 131.3 94 UPC |