Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T00CM03227
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2001 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* OK TO TILE | |
| 03/28/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999* 1) SUPPORT M/C CABLE AS PER CODE 2) SUPPORT FLEX CONDUIT AS PER CODE | |
| 03/21/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | #130 SUPPORT MC CABLE AS PER CODE, #140 JUNCTION BOX NOT MADE UP SUPPORT MC CABLE AS PER CODE #150 JUNCTION BOX NOT MADE UP SUPPORT MC CABLE AS PER CODE #160 SUPPORT MC CABLE AS PER CODE SUPPORT USING INDEPENDANT ELECTRICAL SUPPORT WIRES 300-11 #180 USE INDEPENDANT SUPPORT WIRES 300-11 SUPPORT MC CABLE AS PER CODE. ALL UNITS NO EXIT SIGNS |