Permit: T00CM03225

Parcel: 13604818A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T00CM03225

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/26/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*OK FOR C OF O
07/25/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) THE VENT ON THE CONDENSATE TRAP MUST BE DOWNSTREAM OF THE TRAP. 2.) PAINT EXPOSED PVC W/ LATEX PAINT. 3.) DISCONNECT NEED AN INSIDE COVER PLATE 4.) USE REDWOOD OR PRESSURE TREATED WOOD UNDER CONDENSOR & ANCHOR TO WOOD. 5.) PROVIDE A RAINTITE COVER OVER CONDENSOR.