Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/27/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 07/03/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 06/19/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.NEED 3' WORKING CLEARENCE IN FRONT OF SERVICE EQUIPMENT2.) SUPPORT CONDUIT BELOW GUTTERS 3.) LABELS PANEL 4.) IDENTIFY GROUND CONDUCTOR 5.) BOND CONDUCTOR TO BE ACCORDING TO 250-66 6.) BOND GUTTER ENCLOUSER 7.) NEED TO SEE BOND TO BUILDING STEEL. 8.) NEED TO VERIFY UPPER/GROUNDRODS. 9.) NEED TO VERIFY GAS & WATER BONDS |
| 05/30/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1)WALL ROUGH OK.NO PANELS OR SERVICE OR SERVICE EQUIPMENT IN AT THIS TIME. |