Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T00CM03225
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2001 | FRAMING | Approved | IVRS - Inspection 0000* | |
05/17/2001 | FRAMING | Partial Approval | IVRS - Inspection 0000* 1) SPEC. JOIST/STUD CONNECTION (USED 6-#8) 2) 1 1/2" X 3" CLIPS IN ID ON S3.1 DOESN'T ALLOW 1 1/2" OF WELD AFTER THE 3" (LLH) SIDE OF THE CLIP SPANS A 2" JOIST. CAN A SCREW PATTERN SUBSTITUTE FOR THE WELDS? 3) PROVIDE WELD PLATE FOR SPLICES AT STRAP. OR WOULD A SCREW PATTERN BE ALLOWED? (6-#8 USED) |