Permit: T00CM03225

Parcel: 13604818A

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T00CM03225

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
06/04/2001 FRAMING Approved IVRS - Inspection 0000*
05/17/2001 FRAMING Partial Approval IVRS - Inspection 0000* 1) SPEC. JOIST/STUD CONNECTION (USED 6-#8) 2) 1 1/2" X 3" CLIPS IN ID ON S3.1 DOESN'T ALLOW 1 1/2" OF WELD AFTER THE 3" (LLH) SIDE OF THE CLIP SPANS A 2" JOIST. CAN A SCREW PATTERN SUBSTITUTE FOR THE WELDS?
3) PROVIDE WELD PLATE FOR SPLICES AT STRAP. OR WOULD A SCREW PATTERN BE ALLOWED? (6-#8 USED)