Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit: T00CM03174

Parcel: 136240380


Addresses:

6818 E 39TH ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/28/2001 FRAMING Approved IVRS - Inspection 0000*
02/14/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*
02/13/2001 FRAMING Denied IVRS - Inspection 0999*/1. GABLE ENDS TRUSS NEEDS CONTINOUS SUPPORT AT TOP PLATE. 2. HANGER FOR GLU LAM BEAM NOT APPROVED TYPE 3. AT J-BOX BOND THE METAL BOX 4. NEED FULL SIZE 3/4" TEMP. PRESS RELIEF LINE FOR H20 HEATER THRU ROOF WITH PET COCK. 5. NEED COMB/RELIEF DUCTS. 6. P.V.C. H20 LINES INSIDE BLDG. MUST BE OF APPROVED MATERIAL 7. MOVE ROMEX AWAY FROM H20 HEATER FLUE. 8. CONNECT EXHAUST FAN DUCTS 9. NEED GAS LINE PRESS TEST. 10. GROUT BLOCK CONNECT EXHAUST FAN DUCTS. 11. BLOCK 3 SIDES OF ALL MECH DUCTS (DIFUSSERS). 12. MAKE SURE BATHROOM OUTLETS ARE ON A SEPARATE 20 AMP CIRCUIT WILL CHECK AT FINAL. 13. TRUSSES CUT OR BORED (CALL TRUSS MANUFACTURE FOR REPAIR (DON'T CUT OR NOTCH TRUSSES.) 14. UNCOVER TOILET FLANGE. 15. SMOKE DETECTOR? 16. WHERE VENT FOR TOILET AND SHOWER MEET REMOVE VENT "T" FROM HORIZ USE VERT. OR USE DOUBLE SAN "T"