Permit: T00CM03173


Addresses:

3401 E AJO WY

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/30/2002 PLUMBING - FINAL Approved 1.) NO CORRECTIONS MADE SINCE LAST INSPECTION 2.) GILBERT MARTINEZ WITH THE CITY OF TUCSON HAS AGREED TO MAKE NECESSARY CORRECTIONS IN HOUSE." 791-5111 EXT 340. 3.) PLUMBING FINALOK 4.) OK FOR C OF O PENDING ANY OTHER INSEPCTION. 1.) A 2" TRAP MUST BE CONNECTED TO THE 2" TRAP ARM. 2.) A 2" CLEAN OUT MUST HAVE 12" CLEARANCE IN FRONT OF THE CLEAN OUT. 3.) IT WOULD BE NICE IF THE PIPING WAS INSTALLED IN A WORKMANSHIP LIKE MANNER.
01/21/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) ONE MORE TIME A TRAP ARM MAY NOT BE REDUCED. ALSO THE TRAP MUST BE THE SAME SIZE AS THE TRAP ARM TO WHICH IT IS ATTACHED 1003.3 94 UPC 2.) 2" CLEAN OT REUIRES 12" CLEARNACE INFRONT.
01/10/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) TRAP ARM MAY NOT BE REDUCED 3' 5" MAX ON 1 1/2" 5' O" ON 2" 2.) ALL SINKS REQUIRE CLEAN OUTS.
12/28/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) WATER CLOSET REQUIRES 15" MINIMUM FROM CENTER TO OR OBSTRUCTION.2.) CRITICAL LEVEL OF VACUUM BREAKER ABOVE WATER CLOSET IS INCHES MINIMUM. 3.) IF PAN DRAIN IS USED, IT WILL BE HOT WATER. PVC IS NOT APROVED FOR HOT WATER. 4.) FLEX CONNECTOR ON TOP RELIEF DRAIN OK PER CODE ENFORCED AT TIEM THESE PLANS WERE APPROVED.