Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* THESE NOTES FOR ONLY ROOM THAT IS ON EAST END NO ACCESS TO SOUTHEAST ROOM 1. P-TRAP TO BE INSTALLED CORRECTLY 2. CLEANOUT PLUG TO BE INTACT SO NO SEWER GAS CAN LEAK INTO SPACE. 3. CONDENSATE DRAIN CANNOT CONNECT TO A SINK DRAIN, ONLY LAV TAILPIECE, OK APPROVED FLOOR DRAIN OK SINK OK BUILDING EXTERIOR WHERE WATER WILL ABSORB. |
|
| 03/06/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* PIPE SUPPORTS OK. NO PLUMBING PROBLEMS THAT WOULD PREVENT TCO. RECALL FOR FINAL INSPECTION AFTER COMPLETING SINKS. |
|
| 02/26/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/08/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/30/2000 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* SEE NOTE C.O. FOR SINK IS OK |
|
| 08/25/2000 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* I WAS NOT CALLED OUT FOR INTERMEDIATE INSPECTION AND WALLS ARE COVERED C.O. FOR SINK ON WEST SIDE OF OFFICE MUST HAVE 12" MIN OF CLEARANCE TOO BOARD OF CABINET IS OBSTRUCTING |