Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T00CM03154

Parcel: 123071900


Addresses:

2415 E HELEN ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/23/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
02/22/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/1. W/H CIRCUIT TO GARAGE NOT IN OK TO INSULATE AND DRYWALL ALL BUT W/H CIRCUIT.
02/16/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
02/06/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/1. GAS LINE TO KITCHEN CANNOT RUN UNDER SLAB OR BE ENCASED IN MASONRY WITHOUT VENTED SLEVE. 2. PROVIDE ACCESS FOR INSPECTION OF LEDGER RPG PLATES. 3. BEARING WALL BOTTOM PLATE MUST BE NAILED AT 12" O.C. 4. REVISE PLAN FOR ADDED GAS PIPING-NOT ON PLAN. 5. MECHANICAL NOT PER PLAN-REVISE TO AS BUILT AND INCLUDE DUCT SIZES. 6. REVISE PLAN FOR ADDED ELECTRIC IN STORAGE. 7. GUEST HOUSE NOT READY. 8. 2 FLOOR JOIST MISSING OR SPACED IN EXCESS OF 16" O.C. 9. PLAN CALLS FOR TJI BCI JOIST INSTALLED REVISE PLAN AND PROVIDE BCI INSTALLATION INSTRUCTIONS. 10. FLOOR LEDGER BOLTS/NUTS LOOSE. 11. ANCHOR BOLTS AND PA18 STRAPS MISSING FROM CENTRAL BEARING STEM WALL SEC. 4/2. 12. EXTERIOR WALLS MISSING PA 18'S IN STEM SEE 3/2. 13. NAIL PROTECT WIRES FRONT PORCH LEDGE.