Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/23/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 02/22/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/1. W/H CIRCUIT TO GARAGE NOT IN OK TO INSULATE AND DRYWALL ALL BUT W/H CIRCUIT. |
| 02/16/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 02/06/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/1. GAS LINE TO KITCHEN CANNOT RUN UNDER SLAB OR BE ENCASED IN MASONRY WITHOUT VENTED SLEVE. 2. PROVIDE ACCESS FOR INSPECTION OF LEDGER RPG PLATES. 3. BEARING WALL BOTTOM PLATE MUST BE NAILED AT 12" O.C. 4. REVISE PLAN FOR ADDED GAS PIPING-NOT ON PLAN. 5. MECHANICAL NOT PER PLAN-REVISE TO AS BUILT AND INCLUDE DUCT SIZES. 6. REVISE PLAN FOR ADDED ELECTRIC IN STORAGE. 7. GUEST HOUSE NOT READY. 8. 2 FLOOR JOIST MISSING OR SPACED IN EXCESS OF 16" O.C. 9. PLAN CALLS FOR TJI BCI JOIST INSTALLED REVISE PLAN AND PROVIDE BCI INSTALLATION INSTRUCTIONS. 10. FLOOR LEDGER BOLTS/NUTS LOOSE. 11. ANCHOR BOLTS AND PA18 STRAPS MISSING FROM CENTRAL BEARING STEM WALL SEC. 4/2. 12. EXTERIOR WALLS MISSING PA 18'S IN STEM SEE 3/2. 13. NAIL PROTECT WIRES FRONT PORCH LEDGE. |