Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/18/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 06/14/2001 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 06/12/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NO ADDRESS POSTED MUST BE ON BUILDING IN 3" HIGH NUMBERS ON CONTRASTING BACKGROUND VISIBLE, ADDRESS 2415 MUST BE ON HOUSE NOT AT CURB SIDE 2) UNTREATED WOOD CANNOT BE IN CONTACT WITH SOIL OR MASONARY VENT FRAMES |
| 06/01/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NO ADDRESS POSTED, MUST BE ON BUILDING IN 3" HIGH NUMBERS ON CONTRASTING BACKGROUND VISIABLE 2) CRAWL SPACE MUST BE PROTECTED WITH 1/4" MESH GRILL COVER 3) CLOTHES DRYER MUST HAVE 4 PROWN PLUG 4) ALL PLANS AND PRIOR INSPECTION REPORTS AND INSPECTION CARD REQUIRED AT FINAL INSPECTION 5) INSULATION AND STUCCO INSTALLATION CERTIFICATES REQUIRED, STUCCO ON SITE 6) DRIVE GROUND RODS FLUSH TO GRADE 7) ROOF TOP ATTIC ACCESS REQUIRES WEATHER PROOF COVER 8) 2 EACH A/C ELECTRIC DISCONNECTS SUPPORTED BY A SINGLE CONDUIT-NOT ALLOWED-INSTALL AN ANTI ROTATION BRACE |
| 04/23/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/NO ADDRESS POSTED, NO ACCESS |