Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/16/2000 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 10/09/2000 |
FRAMING |
|
Not ready for Inspection |
1. GARAGE SHEAR A. B. AT 48" O.C. ADD BLOCKS FOR DRYWALL AT FURNACE (SHEAR). 2. ADD BLOCK STAPLE ROMEX AT GARAGE WALL 6" FROM OUTLET. 3. HEADER AT RANGE HOOD STUD CUT. 4. EXHAUST FANS (DUCT) NOT SCURED TO ROOF. 5. NAIL AND PLUMB PONY WALL KITCHEN 6. #4 SHEAR WALL A.B. AT 72" O.C. |