Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/16/2000 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 10/09/2000 |
FRAMING |
|
Not ready for Inspection |