Permit: T00CM03142

Parcel: 10320084B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/06/2001 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000* PROVIDE LISTING ON CPVC VALVES-REVISE PLAN - SERVICE VALVE FOR 1 1/4 WATER - LOCATION OF BLDG SHUT OFF VALVE PROVIDE ACCESS TO COMPRESSION FITTING. PLEASE NOTE WE WILL NEED A REVISED APPROVED PLAN BY ARCHITECT ON 3 STORY BLDG WATER HEATER RELIEF LINE 1ST FLOOR WATER HEATER SEC 608.5 94 UPC
03/05/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*
11/28/2000 PLUMBING - INTERMEDIATE Not ready for Inspection 1) IS URINAL WET VENTED ABOVE WATER CLOSET?
2) RE VENT IN KITCHEN MODEL TOO LOW 3) CLEAN OUT FOR URINAL DISSIMILAR MATREIAL - WRONG COUPLINGS 4) ADD FULL SIZE CLEAN OUT AT END OF MODEL BATHROOM