Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* CORRECTIONS HAVE BEEN MADE |
|
| 12/18/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* SUPPORT CONDUIT IN MIX ROOM SUPPORT CONDUIT ABOVE PANEL AND ON ROOF |
|
| 12/08/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* MIX ROOM UNAPPROVED WIRE FOR COMPUTER SYSTEM COMPUTER SYSTEM NOT RATED TO BE IN MIX ROOM CORD COMING OUT OF PAINT MIXER TO BE TERMINATED PROPERLY WITH CORRECT FITTING IN EXPLOSION J-BOX SUPPORT 1/2" CONDUIT GOING FROM SW AT MIX ROOM ROOF SUPPORT 3/4" AND 1/2" EMT ON ROOF DISCONNECT AT BONANZA USE GREEN SCREW TO BOND GROUNDS TO CON BONANZA UNIT HAS 50 AMP FUSE #10 WIRE AND 40 AMP RELAY SHOULD BE 20 A OR VERIFY |