Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/02/2000 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 09/26/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* |
| 09/25/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. PROVIDE 1/2" AB'S AT SHEAR WALL IN GARAGE. 2. PROVIDE 1/2" AB'S AT FRONT OF GARAGE ENTRY. 3. CLAMP 4X4 POST IN GARAGE. 4. BLCOK MECHANICAL 3 SIDES AT MASTER W/C. 5. COMPLETE W/C RINGS. 6. PROVIDE 12" CLEARANCE BETWEEN PEX AND LIGHT CANS. 7. STRAP GLUE LAM TO EXTERIOR WALL (HORIZONTALLY) AT ENTRY (ABOVE). 8. MISSING HOLD DOWN (INSIDE) TO SHEARWALL AT GUEST BATH. 9. TUB DIVERTER NOT PROPERLY SUPPORTED. 10. ELECTRIC REPAIR AT ISLAND NOT APPROVED. 11. GAS LINE AT ENTERTAINMENT CENTER NOT COMPLETE ALSO OVER NOTCHED DOUBLE TOP PLATE--PROVIDE REPAIR. |