Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
09/05/2001 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*1.) RELOCATE DUCT SMOKE DETECTORS TO THE RETURN PLENUN AS PER 2000 IMC 2. )PROVIDE WIRING OF FIRE/SMOKE DAMPER TO BLDG. ALARM SYSTEM. SEE SEC 607.5.4.1. 2000 IMC LEAVE OUT TILES UNDER PLENUM FOR INSPECTION ON DUCT DETECTORS 3.) INSTALL FIRE/SMOKE DAMPER IN A FIRE WALL.
08/22/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*TROPEZING UNDER SUPPLY/RETURN DROPS. NOTE! CHECK WITH ELECT CONTR. MAKE SURE FUSE PKG. IS IN AGREEMENT W/UNIT DATA PLATE DO NOT WAIT FOR FINAL.