Permit: T00CM03003

Parcel: 10607030A


Addresses:

1351 W PRINCE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/11/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/09/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK WALK IN BOX, OK ROOF, 1. CANNOT PASS A CORD THROUGH STRUCTURE. 2. BOND ENCLOSURE & DOUBLE LUGGING AT COMPRESSOR DISCONNECT.
09/25/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK FLOOR JUNCTION TO SHELVES, OK CASH WRAPS 3 OK TOWER OK PHARMACY,OK TRAINING ROOM, OFFICE, LOCKER ROOM. TOP OF WALK IN BOX NOT READY ( DONT FORGET TO SEAL 2.) FINISH COMPACTORS. 3.) CAN NOT USE SHEET METEAL SCREW FOR GROUND LUG 250-8 CLEAN SURFACE UNDER LUG 250-12 CHECK IF A/C UNIT LISTED TO PASS LINE SIDE ELECTRIC NEED TO RUN RACEWAY SYSTEMS WHERE NOT LISTED.
09/10/2001 ELECTRIC - FINAL Partial Approval 1.) SIZE BONDING JUMPER PER CODE 250-102 C 2.) NEED BONDING DEVICE BOTH SIDES OF NIPPLE BEFORE 1ST DISCONNECTING MEANS 250-94. 3.) IDENTIFY ISOLATED GROUND AS PER PLAN GREEN W/YELLOW TRACER. 4.) SUPPORT WIRES TO BE ATTACHED AT BOTH ENDS 300-11 5.) LOOSE FITTINGS AT FLOODS. OK BREAKER AND CONDUCTORS SIZING AT "MDP" AS MARKED ON PLANS.
09/04/2001 ELECTRIC - FINAL Denied 1.) USE APPROVED WIRING METHODS 2.) CORRECTLY LABEL PANEL 3.) VERIFY LICENSED ELECTRICAL CONTRACTOR PERFORMING WORK A REFEE HAS BEEN ASSESSED.