Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/11/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/09/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*OK WALK IN BOX, OK ROOF, 1. CANNOT PASS A CORD THROUGH STRUCTURE. 2. BOND ENCLOSURE & DOUBLE LUGGING AT COMPRESSOR DISCONNECT. |
| 09/25/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*OK FLOOR JUNCTION TO SHELVES, OK CASH WRAPS 3 OK TOWER OK PHARMACY,OK TRAINING ROOM, OFFICE, LOCKER ROOM. TOP OF WALK IN BOX NOT READY ( DONT FORGET TO SEAL 2.) FINISH COMPACTORS. 3.) CAN NOT USE SHEET METEAL SCREW FOR GROUND LUG 250-8 CLEAN SURFACE UNDER LUG 250-12 CHECK IF A/C UNIT LISTED TO PASS LINE SIDE ELECTRIC NEED TO RUN RACEWAY SYSTEMS WHERE NOT LISTED. |
| 09/10/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
1.) SIZE BONDING JUMPER PER CODE 250-102 C 2.) NEED BONDING DEVICE BOTH SIDES OF NIPPLE BEFORE 1ST DISCONNECTING MEANS 250-94. 3.) IDENTIFY ISOLATED GROUND AS PER PLAN GREEN W/YELLOW TRACER. 4.) SUPPORT WIRES TO BE ATTACHED AT BOTH ENDS 300-11 5.) LOOSE FITTINGS AT FLOODS. OK BREAKER AND CONDUCTORS SIZING AT "MDP" AS MARKED ON PLANS. |
| 09/04/2001 |
ELECTRIC - FINAL |
|
Denied |
1.) USE APPROVED WIRING METHODS 2.) CORRECTLY LABEL PANEL 3.) VERIFY LICENSED ELECTRICAL CONTRACTOR PERFORMING WORK A REFEE HAS BEEN ASSESSED. |