Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/21/2000 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 09/20/2000 |
BUILDING - FINAL |
|
Denied |
1. CLEARANCE FOR FURNACE NOT IN COMPLIANCE WITH UMC 908 OR PLANS. 2. ELECTRICAL WIRE AT ATTIC ACCESS IS TORN AND IS NOT TO BE INSTALLED THRU ACCESS ENTRANCE. 3. NO ANTI TILT DEVICE INSTALLED A RANGE. ALL ITEMS HAVE NOT BEEN ADDRESSED SUPER INDTENDENT WAS ADVISED TWICE ON PREVIOUS INSPECTIONS REINSPECTION FEE REQUIRED. |
| 09/19/2000 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1. THE ATTIC FURNACE DOES NOT COMPLY WITH THE UMC 908 AND WITH APPROVED PLANS SHEET M1. 2. PROVIDE 1" CLEARANCE FROM COMBUSTIBLES AT FURNACE FLUE. 3. SUPPORT GAS LINE PER UPC. 4. MAS STRAP AT BACK PATIO DOOR NOT NAILED UP. 5. PROVIDE A CAP AT GAS VALVE FOR STOVE OR HOOK UP STOVE WITH ANTI-TIP IN PLACES. |
| 09/15/2000 |
BUILDING - FINAL |
|
Denied |
FURNACE GAS LINE NOT HOOKED UP FLEX CANNOT EXCEED 3'. ROMEX OBSTRUCTING ACCESS TO ATTIC COVER ROMEX DAMAGED. REPLACE ACCORDINGLY. PROVIDE GAS PRESSURE TEST AFTER INSTALLATION. REMOVE COMBUTIBLE MATERIAL FROM FLUE VENT. |