Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/17/2001 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*PAINT EXPOSED PVC W/LATEX PAINT O.K. FOR C OF O. |
| 03/16/2001 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 03/01/2001 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1) PERMANENTLY LABEL EQUIPMENT ON ROOF 2) MARK DATA PLATES WITH PROPER HEAT STRIP INSULATED AND FUSE UNITS ACCORDINGLY 3) PAINT ALL EXPOSED PVC WITH LATEX PAINT. 4) EXSISTING CONDENSATE DRAIN LINE MUST STEP UP TO 1" AFTER SECOND UNIT. IF TERMINATING INTO THE SIDE OF A WASTE VENT YOU MUST USE AN APPROVED FITTING AND VENT MUST BE MINIMUM 2". 5) SHEET METAL SUM SHIELDS OVER CANVAS CONNECTORS NOT COVERING PROPERLY. 6) PROVIDE OUTSIDE AIR ON 2 UNITS ON ROOF. OK FOR TEMP C OF O |