Permit: T00CM02983

Parcel: 13329015B


Addresses:

8655 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/17/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*PAINT EXPOSED PVC W/LATEX PAINT O.K. FOR C OF O.
03/16/2001 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*
03/01/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000* 1) PERMANENTLY LABEL EQUIPMENT ON ROOF 2) MARK DATA PLATES WITH PROPER HEAT STRIP INSULATED AND FUSE UNITS ACCORDINGLY 3) PAINT ALL EXPOSED PVC WITH LATEX PAINT. 4) EXSISTING CONDENSATE DRAIN LINE MUST STEP UP TO 1" AFTER SECOND UNIT. IF TERMINATING INTO THE SIDE OF A WASTE VENT YOU MUST USE AN APPROVED FITTING AND VENT MUST BE MINIMUM 2". 5) SHEET METAL SUM SHIELDS OVER CANVAS CONNECTORS NOT COVERING PROPERLY. 6) PROVIDE OUTSIDE AIR ON 2 UNITS ON ROOF. OK FOR TEMP C OF O