Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2001 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000* WILL CHECK FIRE DAMPER IN CORRIDOR ON FINAL. ACCESS THRU CLERGICAL OFFICE | |
| 03/16/2001 | MECHANICAL - ABOVE CEILING | Partial Approval | NEED TO SEE FIRE DAMPER OPENINGS PRIOR TO DAMPER INSTALLATION | |
| 02/05/2001 | MECHANICAL - ABOVE CEILING | Partial Approval | CORRECTIONS HAVE BEEN MADE | |
| 02/01/2001 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection 0999* INSULATE T-WYES AND ALL BARE METAL ON SUPPLY AND RETURN DUCTS STRAP FLEX DUCT UP OFF OF LIGHTS AND GRID WIRE SMOKE DETECTORS PROVIDE SUPPORT ON RETURN DIFFUSERS AND PLEURMS AT CEILING CURBS FOR A/C EQUIPMENT NOT PER PLANS |