Permit: T00CM02977

Parcel: 10511061R

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T00CM02977

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/17/2000 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*
10/24/2000 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
PLUMBING CORRECTIONS, CAST IRON AND COPPER IN GRID RETURN AIR PLENIUM OK
ALL HOLES, REAR OF SPACE IN LOWER LID, AROUND SPRINKLER PIPING, ETC NEED TO BE SEALED
ALL AIR RETURNING FROM SPACE IS RETURNING FROM THE 2. 48"X30" FIRE DAMPERED OPENING'S IN FACE OF LOWER LID ALL HOLES IN THIS LOWER LID NEED TO BE SEALED
10/12/2000 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
PVC VACUM LINE
ABS WET VENT LINES
ABOVE GRID IN PLENIUM
NEEDS TO BE COPPER AND CAST IRON
09/07/2000 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*