Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T00CM02977
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/15/2000 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* OK TO TILE |
|
10/23/2000 | ELECTRIC - ABOVE CEILING | Partial Approval | 10/23/00 PLUMBING CAN NOT BE SUPPORTED FROM CONDUIT PROTECT FIXTURE WHIP FROM PLUMBING STRAP M/C FOR SIGN NEED TO SEE MAKE UP AT JUNCTION BOXES WITH BOTH M/C AND A/C CABLES |
|
10/10/2000 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0240* SECURE MC CABLE WITHIN 12" OF J-BOX PER NEC AND 4 1/2" THEREAFTER SIESMICS MISSING ON FIXTURES LEAVE 8' LADDER TO VERIFY PROPER MC CONNECTORS ETC J-BOXES OVERFILLED ISOLATE ELEC CONDUIT FROM PLUMBING LINES |
|
09/06/2000 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999* SUPPORT CONDUIT INDEPENDENT OF CEILING SUPPORTS NOTE #2/300-11 WORKING CLEARENCES IN FRONT OF JUNCTION BOXES SUPPORT FLEX CONDUITS AND M/C CABLE AS PER CODE TIGHTEN CONDUIT FITTINGS CAON NOT USE RACEWAY TO SUPPORT OTHER CONDUITS M/C CABLES FLEX 300-11 SUPP |