Permit: T00CM02977

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T00CM02977

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/15/2000 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
OK TO TILE
10/23/2000 ELECTRIC - ABOVE CEILING Partial Approval 10/23/00 PLUMBING CAN NOT BE SUPPORTED FROM CONDUIT
PROTECT FIXTURE WHIP FROM PLUMBING
STRAP M/C FOR SIGN
NEED TO SEE MAKE UP AT JUNCTION BOXES WITH BOTH M/C AND A/C CABLES
10/10/2000 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0240*
SECURE MC CABLE WITHIN 12" OF J-BOX PER NEC AND 4 1/2" THEREAFTER
SIESMICS MISSING ON FIXTURES
LEAVE 8' LADDER TO VERIFY PROPER MC CONNECTORS ETC
J-BOXES OVERFILLED
ISOLATE ELEC CONDUIT FROM PLUMBING LINES
09/06/2000 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*
SUPPORT CONDUIT INDEPENDENT OF CEILING SUPPORTS NOTE #2/300-11
WORKING CLEARENCES IN FRONT OF JUNCTION BOXES
SUPPORT FLEX CONDUITS AND M/C CABLE AS PER CODE
TIGHTEN CONDUIT FITTINGS
CAON NOT USE RACEWAY TO SUPPORT OTHER CONDUITS M/C CABLES FLEX 300-11
SUPP