Permit: T00CM02977

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T00CM02977

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/18/2000 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
OK WALLS
09/14/2000 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
M/C CABLE TO BE SUPPORTED WITH APPROVED METHOD THEN APPROVED
MOVE M/C CABLE OUT OF CHANNEL BATHROOM ABOVE LIGHT
TIGHTEN CONDUIT FITTINGS
NEED INSULATED GROUNDED CONDUCTOR W PATIENT CARE ARE. 517-13
M/C OK AS IDENTIFYED
09/08/2000 ELECTRIC - INTERMEDIATE Not ready for Inspection CANCELED BY OFFICE 9:45
09/06/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
NEED APPROVED PLANS ON JOB
CORRECTLY SUPPORT RACE WAYS AS PER CODE
CORRECTLY SUPPORT M/C CABLE AS CODE
MOVE M/C CABLE OUT OF CENTER OF STUD CHANNEL OR PROTECT WITH STRAPS AS PER CODE
TIGHTEN CONDUIT FITTINGS
ALL PATIENT CARE AREA TO MEET REQUREMENTS OF ART 517-13