Permit: T00CM02932

Parcel: 12113649D

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
10/18/2000 ELECTRIC - ABOVE CEILING Approved 10/18/00 APPROVED
10/17/2000 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*
SUPPORT J-BOXES
BEND OUT TABS ON 2X4 FLOURESCENT
FIXTURES OR SCREW TO GRD,
SUPPORT MC AND FLEX WITHIN 1' OF EACH J-BOX AND EVERY 6' DO NOT USE GRID WIRE THAT IS INTENDED FOR GRID SUPPORT EXCEPT FOR FIXTURE WHIPS 6' OR LESS
09/18/2000 ELECTRIC - ABOVE CEILING Partial Approval HARD CEILING IN LOBBY OK