Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T00CM02929

Parcel: 125151100


Addresses:

45 E CALLE BELLEZA


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T00CM02929

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2001 FRAMING Approved IVRS - Inspection 0000*
09/17/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) FIRE BLOCK SOFFIT IN HALL BATH 2) SUPPORT CAST DOWN AT HALL BATH 3) SMOKE DETECTOR CANNOT BE WITHIN 36" OF AIR REGISTERS 4) GROUND ALL METAL ELECTRIC BOXES 5) MAKE UP ALL GROUNDS AND SECURE WITH MECHANICAL FASTENERS 6) DOUBLE LUGGING OF CIRCUIT BREAKERS NOT ALLOWED 7) WATER HEATER IN BASEMENT NOT VENTED TO OUTSIDE 8) INSTALL TWO EACH 8' GROUNDS AT LEST 6' APRART AND CONNECT TO SERVICE PANEL WITH CONTINOUS CONDUCTOR 9) ADDRESS REQUIRED ON SERVICE ENTRANCE PANEL 10) ELECTRICAL BOND REQUIRED ON GAS LINE 11) INSTALL PROPER SPLIT LUG ON DUEL LUGGED WIRES IN MAIN SUB PANEL 12) WEST SIDE OF KITCHEN POCKET DOOR REQUIRES 2 TRIMMERS
04/02/2001 FRAMING Partial Approval IVRS - Inspection 0000*/1. UNTREATED WOOD CANNOT BE WITHIN 18" OF SOIL 2. NOTE: ALL OTHER FRAME IS OK BUT CANNOT APPROVE UNTIL ALL ELECTRIC PLUMBING AND MECH IS COMPLETE ROOF SHEATHING NOT READY.