Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T00CM02929
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2001 | FRAMING | Approved | IVRS - Inspection 0000* | |
09/17/2001 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) FIRE BLOCK SOFFIT IN HALL BATH 2) SUPPORT CAST DOWN AT HALL BATH 3) SMOKE DETECTOR CANNOT BE WITHIN 36" OF AIR REGISTERS 4) GROUND ALL METAL ELECTRIC BOXES 5) MAKE UP ALL GROUNDS AND SECURE WITH MECHANICAL FASTENERS 6) DOUBLE LUGGING OF CIRCUIT BREAKERS NOT ALLOWED 7) WATER HEATER IN BASEMENT NOT VENTED TO OUTSIDE 8) INSTALL TWO EACH 8' GROUNDS AT LEST 6' APRART AND CONNECT TO SERVICE PANEL WITH CONTINOUS CONDUCTOR 9) ADDRESS REQUIRED ON SERVICE ENTRANCE PANEL 10) ELECTRICAL BOND REQUIRED ON GAS LINE 11) INSTALL PROPER SPLIT LUG ON DUEL LUGGED WIRES IN MAIN SUB PANEL 12) WEST SIDE OF KITCHEN POCKET DOOR REQUIRES 2 TRIMMERS | |
04/02/2001 | FRAMING | Partial Approval | IVRS - Inspection 0000*/1. UNTREATED WOOD CANNOT BE WITHIN 18" OF SOIL 2. NOTE: ALL OTHER FRAME IS OK BUT CANNOT APPROVE UNTIL ALL ELECTRIC PLUMBING AND MECH IS COMPLETE ROOF SHEATHING NOT READY. |