Permit: T00CM02887

Parcel: 119034750

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
05/13/2004 BUILDING - FINAL Approved IVRS - Inspection :*
05/07/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PAINT AB'S PLASTIC VENTS ON ROOF 2) OUTSIDE HOSE BIBS MUST HAVE NON REMOVABLE ANTI-SIPHON VALVES 3) INCORRECT COLOR CODDING OF WIRES IN SERVICE PANEL. WHITE WIRES CANNOT BE HOT. PUT RED OR BLACK TAPE ON HOT WHITE WIRES 4) ADDED GARAGE OUTLET MUST BE 18" ABOVE FLOOR 5) BARE BULB LIGHT FIXTURE NOT ALLOWED IN CLOSET 6) OUTLET RT OF RANGE MUST BE GFCI PROTECTED