Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM02843
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/21/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*APPROVED LETER ON LOWER TOTAL VOLTAGE USAGE FROM ENG. OK LETTER OK ON CHANGE FROM OWNER TO FOLLOW. | |
06/04/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) FINISH ITEM #2. OK FOR TEMP C OF O SUBJECT TO BOND. 2.) LIGHTING IN MOSE AREAS IS DIFFERENT THAN PLAN AND ENEGY CODE CACULATIONS. | |
05/14/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) EXIT SIGN NEEDED AT FRONT DOOR. 2.) LIGHTING IN MOST AREAS IS DIFFERENT THAN PLAN AND ENEGY CODE CACULATIONS. 3.) CONDISATE PUMPS HAVE CORD PLUG END CUT OFF AND HARD WIRED INTO A/C DISCONNECT ON UNITS. THIS VIOLATES LISTING AND TERMANATION CONNECTIONS. 110-3,110-14. 4.) PLEASE LABEL PANELS ON OUTSIDE OF COVER AND LABEL BREAKERS. |