Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/22/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 06/28/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - ATTIC 1. MISSING FACE PLATE 2. SUPPORT M/C CABLE CORRECTLY OK TO COVER WALLS |
| 06/28/2000 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 06/27/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. SECURE M/C CABLE WITHIN 12 OF BOX OF FIXTURES 2. FHA STRAPS TO PROTECT WIRING 3. MISSING 4 SQ COVER 4. BOXES MUST BE INDEPENTLY SUPPORTED 300-11 5. NEED MAINTANCE RECEPTACLE IN ATTIC 210-63 6. M/C CABLE NANNOT BE SUPPORTED OFF OF M/C CABLE SECURE CORRECTLY 7. SUPPORT M/C CABLE ABOVE PANEL 8. BRAKERS MAX HEIGHT 67 9. NEED LETTER FROM ENGINEER APPROVING USE OF M/C CABLE |
| 06/27/2000 |
ELECTRIC - INTERMEDIATE |
|
Denied |
DENIED |