Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 09/27/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* PANEL LE DOESN'T HAVE THE REQUIRED WORKING CLEARANCE DUE TO THE NEW WALLS ENCLOSING THE ELEC. PANELS AND TRANSFORMERS EACH PANEL NEEDS A MIN WIDTH OF 30" X 36" DEEP |
|
| 09/13/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* PARTIAL ELECTRICAL FINAL REMAINING POWER POLES NEED TO BE INSTALLED FOR FINAL OK TO OCCUPY |