Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2000 | ELECTRIC - ABOVE CEILING | Approved | 10/24/00 ABOVE CEILING APPROVED | |
| 10/20/2000 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | 10/20/00 2X4 LAY IN FIXTURES REQUIRE 2 SIEMIC WIRES, SCREW FIXTURES TO GRID OR INSTALL TABS. SUPPORT EMT WITHIN 3' EACH J-BOX COMPLETE MAKE UP OF J-BOXES |
|
| 08/31/2000 | ELECTRIC - ABOVE CEILING | Partial Approval |