Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM02760
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/27/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
10/30/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*OK #1,2,4,5, ON 10-10-01. 15 DAY TO COMPLY. 1.) PROVIDE APPROVED LETTER DETERING PARKING CANOPY LIGHTING 2.) REMOVE OMITED UP LIGHTING AS ON PLANS. 3.) FIXTURE COUNTS DIFFER FROM LETTER DATED 6-7-01 FOR /ACRE PLEASE RECOUNT AND REFIGURE. 4.) FIXTURE "Q" ON BUILDING 1630 ARE INSTALLED DIFFERENT THAN PLANS INSTALL AS PLANS OR REVISE PLANS. | |
10/10/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) NEED APPROVED PLANS ON SITE. 2.) WEATHER PROOF ELECTRICAL SPLICES W/PULL BOXES 3.) UP LIGHTING TO MEET LIGHTING CODES 4.) NEED ACCESS TO PULL BOXES IN PARKING LOT 5.) PLEASE HAVE ELECTRICIAN PRESENT NEED TO INSPECT PANEL CONNECTIONS | |
04/12/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* OK TEMP C OF O | |
04/11/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) MISSING OUTSIDE LIGHTING - NEED LETTER FROM ENGINEER REGUARDING DELEATION OF FIXTURES 2) NEED TO SEE APPROVED BY CITY SET OF LIGHTING PLANS NOTE: LETTER FOR TEMP C OF O HAS BEEN RECEIVED BY E DUARTE REGUARDING PARKING LOT LIGHTING WITH INTENT TO CHANGE WITHIN 30 DAYS. NO REFERENCE TO GROUND LIGHTING WAS MADE- CALLED AND SPOKE WITH RMAJUTA-EDUARTE SAID TO REMOVE UP LIGHTS FOR C OF O |
|
04/02/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) MISSING BATH LIGHT FIXTURES 2) IDENTIFY SUPPORT ELECTRIC WIRING METHODS 300-11 3) SUPPORT NM CABLE AS PER CODE-WITHIN 12" 4) MISSING OUTSIDE LIGHTING- WALL 5) METAL HALIDE LIGHTING NOT APPROVED FOR THIS AREA OK ROOF | |
03/20/2001 | ELECTRIC - FINAL | Denied | USE OF METAL HALIDE FIXTURES ARE PROHIBITED ORDINANCE #8210 SEC 5. NEED TO SUBMIT A DRAWING AND SPEC SHEET FOR REVIEW AND APPROVAL OF ALL LIGHTING |