Permit: T00CM02745

Parcel: 11616237A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T00CM02745

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/07/2000 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
10/26/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
10/26/00 GROUND SCREW TO HAVE FULL SURFACE CONTACT NOT ON LOCKNUT
NEED 2 APPLIANCES CIRCUITS IN KITCHEN 20 AMP 210-52
ALL KITCHEN RECEPTACLES TO BE GFCI PROTECTED 210-8
JBATH GFCI TO BE ON IT'S OWN CIRCUIT 20 AMP 210-52
NEED DISCONNECTING MEANS FOR WATER HEATER 422
DERATE CONDUCTORS IN CONDUIT 310-15
NEED GAS BOND 250-104